Reduced Voltage Motor Starters | Electrical Academia (2024)

Induction motors draw very large currents when started at full voltage. Thus, it is desirable, especially for large motors, to start them at reduced voltage to keep the starting current low. Reduced voltage motor starting methods include resistance starting, reactance starting, autotransformer starting, wye-delta starting, part-winding starting, and electronic soft starting. Autotransformer, wye-delta, and electronic soft starting will be discussed in this section.

Autotransformer Starting

This method employs autotransformers in the lines between the source and the motor to reduce the motor starting voltage and thus the inrush current.

Taps are provided that allow the user to select 50%, 65%, or 80% of the line voltage. This reduces the starting current to a similar percentage of the full-voltage starting current.

It should be remembered that motor torque varies with the square of the voltage. Therefore, for the voltage settings listed above, the starting torque will be reduced to 25%, 42%, and 64% of rated starting torque, respectively.

Figure 1(a) illustrates the concept of autotransformer starting using three single-phase auto­ transformers connected in a wye configuration.

It is also possible to use only two autotransformers by connecting them in an open-delta. Figure 1(b) shows the method of two single-phase autotransformers connected in open-delta.

In either case, the motor is started with reduced voltage from the autotransformer and then is shifted to full voltage to run. To accomplish the transition from reduced voltage to full voltage requires a control circuit.

FIGURE 1: Autotransformer starting of an induction motor.

Autotransformer starting may be either open-transition or closed-transition.

In closed-transition starting, the motor is never removed from the supply during the starting period. In open-transition starting, the motor may be temporarily disconnected when moving from one incremental voltage to another, which can cause current surges. Closed-transition starting is a better method but costs more. Figure 2 illustrates closed-transition starting.

FIGURE 2: Closed-transition autotransformer starting.

The control circuit consists of time-delay relay TD1, two start contactors SI and S2, and one run contactor R. Pressing the start push button will result in the following sequence of events:

  • Time-delay relay TD1 is energized, closing the instantaneous contacts TD1-1 and TD1-2. TD1-1seals the start switch, and TD1-2 enables the lower portion of the ladder diagram.
  • Because contacts R and TD1-4 are normally closed, contactor SI is energized.
  • Contact Sl-1 closes to energize contactor S2.
  • All SI and S2 contacts in the power circuit close, which connects the three autotransformers into a wye. The motor is connected to the mid­ point tap on the autotransformer, so the motor starts at reduced voltage.
  • After a preset time delay, TD1-3 closes and TD1-4 opens. Contactors SI and S2 are de­ energized, removing the autotransformers from the circuit, and contactor R is energized, which applies full voltage to the motor.

Wye-Delta Starting

We know that three impedances connected in Wyereceive a lower phase voltage than if they are connected in delta. That is the principle behind wye-delta starting.

Figure 3 illustrates the method of wye-delta starting. The motor windings are first connected in a wye configuration to start the motor. As a result, only 58% of the line voltage is applied to each phase of the motor.

After a preset time delay, the motor windings are reconnected in a delta configuration so that full line voltage is applied to the motor windings. The motors used for wye-delta starting are wound with 6 or 12 leads at the motor terminal box so the motor phase leads can be connected in either wye or delta.

FIGURE 3: Wye-delta starting.

The wye-delta starter is inherently open-transition. Using a wye-delta starter reduces the starting current to about one-third of the full-voltage, locked-rotor current but also limits the starting torque to one-third of the normal locked-rotor torque.

The control circuit of Figure 3 consists of time-delay relay TD1, main contactor M, start contactor S, and run contactor R. Pressing the start push button will result in the following sequence of events:

  • Contactor M is energized. Contact Ml closes to seal the start switch and enable the lower portion of the ladder diagram.
  • Time-delay relay TD1 is energized. Since contacts TD1-2 and R1 are normally closed, contactor S is energized. Contactor R is not energized since the NC relay SI and NO relay TD1 are both open.
  • All of the M and S contacts in the power circuit close to starting the motor in a wye configuration.

The M contacts connect the power source to the motor. The S contacts connect all three motor windings together at the center of the wye.

  • After a preset time delay, contact TD1-1 closes and contact TD1-2 opens. Contactor S is de­ energized, and contactor R is energized.
  • In the power circuit, contacts S open, undoing the wye connection, and contacts R close, connecting the motor windings in a delta configuration.

Electronic Soft Starting

Commercially available, adjustable voltage systems use phase-controlled Thyristors or silicon- controlled rectifiers (SCRs). By controlling all three phases ofthe motor, we can start the motor with reduced voltage and ramp up to full voltage. Figure 4 shows a soft starter on the left and an electronic motor starter on the right.

FIGURE 4: Soft starter and electronic motor starter.

Both are capable of providing a reduced-voltage start to the motor; however, the electronic motor starter does not need a conventional motor starter to operate but the soft starter does. Figure 5 shows, conceptually, an electronic soft starter.

FIGURE 5: Electronic soft-starter concept.

Figures 6 and 7 illustrate the effect of the electronic soft starter on various motor characteristics. By using the electronic soft starter, the motor starting current, in this illustration, is limited to less than half the rated starting current, and the motor voltage is slowly ramped up to rated voltage.

FIGURE 6: Motor characteristics with the hard start.

FIGURE 7: Motor characteristics with soft start.

Thus, the term soft start. The effect on torque and speed are also shown. Simple soft starters generally have an adjustable setting to control the speed at which the voltage is ramped up and the motor starts.

Electronic motor starters may offer relatively elaborate programming capabilities to adjust not only the time of acceleration but also the shape of the voltage ramp. They also offer communication capabilities to connect to PCs and PLCs.

Reduced Voltage Motor Starters | Electrical Academia (2024)

FAQs

How does a reduced voltage motor starter work? ›

A simple and common method of starting a motor at reduced voltage is used in primary resistor-type starters. In this method, a resistor is connected in series in the lines to the motor. As current flows through the resistors, a voltage drop occurs, and the voltage at the motor terminals is reduced by that amount.

What is the most common method of reduced voltage starting? ›

Final answer: The most common method of reduced-voltage starting used with solid-state reduced voltage controllers is the ramp start.

What are the disadvantages of reduced voltage starter? ›

The disadvantage of using reduced voltage starting in motors is that as the voltage is low during startup, the torque is also low at starting. This method of starting may not be suitable for applications such as conveyors, lifts, etc which require the motor to start with the load.

What is the difference between soft starter and reduced voltage starter? ›

Since the speed of an operating motor depends on frequency, a soft starter cannot be used for speed control. Reduced voltage can limit the starting current of a motor, but it will not reduce rpm once the unit has started. Actually, a motor overheats with reduced voltage, and this affects its service life.

Which choice is a reason why reduced voltage starting is used? ›

Purpose of a RVSS

RVSS provides a smooth, controlled start and stop you can use to reduce stress on motors and mechanical systems, reduce voltage drops in facilities, and reduce electrical demand charges.

Which reduced voltage starting is typically not used for? ›

The correct option is : d) wye-delta motors. Reduced voltage starting is typically not used for wye-d...

How to reduce voltage drop during motor starting? ›

conventional motor starters, reduce voltage drops by installing power factor correction capacitors at the points of use. electronic adjustable speed drive, the drive can compensate for voltage discrepancies as long as the input voltage is within the operating range of the drive.

Are soft starters bad for motors? ›

Soft starts reduce mechanical shock and peak current demand during startup and can help improve motor life and reliability. However, the wrong soft starter may cause unnecessary strain on motors during the already stressful period of startup, potentially leading to premature wear or damage.

Why does a large DC motor require a reduced voltage starter? ›

This high current will cause mechanical stress and also heats the winding and result in damage to windings. Not only this, a sudden voltage drop will affect the other machines in same supply line. Hence to limit starting current, reduced voltage is applied with the help of starter during initial starting.

What is a star delta starter? ›

A star delta starter, also known as a Wye-Delta starter, is an electrical control circuit used to start and control the speed of three-phase induction motors. It is widely employed in various industries where motors with high power ratings are used, such as manufacturing plants, refineries, and mining operations.

What are reduced voltage starters? ›

What are Reduced Voltage Soft Starters? In short, it is any device, used with an electrical motor that, instead of flipping a switch and bringing it to full power, it gradually applies voltage, allowing the motor to control the electrical load and torque of that startup.

How many types of reduced voltage AC starters are there? ›

This course will cover the starting characteristics of AC induction motors and the impact of using 5 methods for reduced voltage starters. The National Electrical Manufacturers Association (NEMA) defines different designs for AC induction motors, designated as design A, B, C and D.

What are the different types of VFD starters? ›

Three types of VFDs exist: Voltage-Source Inverter (VSI), Current-Source Inverter (CSI), and Pulse Width Modulation Inverter (PWM). VSI is the most common type of VFD, where a simple diode circuit is used to get the DC signal from the AC signal and has a capacitor that stores energy.

How many types of starters are there? ›

The two main types of starters are Manual Starters and AC Magnetic Motor Starters, commonly known as Motor Starters.

Top Articles
Latest Posts
Article information

Author: Msgr. Refugio Daniel

Last Updated:

Views: 6071

Rating: 4.3 / 5 (54 voted)

Reviews: 93% of readers found this page helpful

Author information

Name: Msgr. Refugio Daniel

Birthday: 1999-09-15

Address: 8416 Beatty Center, Derekfort, VA 72092-0500

Phone: +6838967160603

Job: Mining Executive

Hobby: Woodworking, Knitting, Fishing, Coffee roasting, Kayaking, Horseback riding, Kite flying

Introduction: My name is Msgr. Refugio Daniel, I am a fine, precious, encouraging, calm, glamorous, vivacious, friendly person who loves writing and wants to share my knowledge and understanding with you.